Home / Products / 19-Outlet British BS 1363 Vertical Rack PDU, 230 V 63 A, Hydraulic Breaker, 0U
19-Outlet British BS 1363 Vertical Rack PDU, 230 V 63 A, Hydraulic Breaker, 0U
Basic PDU

19-Outlet British BS 1363 Vertical Rack PDU, 230 V 63 A, Hydraulic Breaker, 0U

Quick Answer19-Outlet British BS 1363 Vertical Rack PDU, 230 V 63 A, Hydraulic Breaker, 0U — an IDCPDU Basic PDU for data-centre and equipment-room racks.
  1. Local socket pattern, not an adapter job — Outlets are the pattern already installed in the building, so equipment cords go straight in — one joint less to loosen inside a live rack.
  2. 0U vertical — no rack units consumed — The strip hangs on the rear post, so every U stays available for servers.
  3. Breaker ahead of the outlets — A fault trips inside the strip, not at the upstream panel — the rest of the row keeps serving traffic.
  4. Passive build, nothing to fail — No metering board and no switching relay inside — for a basic strip that means fewer parts that can take a rack down.

Tel: +86-574-63783045 · ricky@idcpdu.com

Contact Us
SHARE:

Product Description

  • 19 British BS 1363 sockets in a 0U strip
  • 230 V, 63 A input, 13 A per outlet
  • Hydraulic magnetic breaker with status indicator
  • At 60 × 85 mm the body fits the rear channel of a 42U cabinet on 1358 mm centres and leaves both cable managers free; the sockets face the rear aisle so cords drop straight into the vertical manager.
  • Every BS 1363 outlet is shuttered and fused to the British standard, so a 13 A fuse protects each appliance lead — the reason UK racks rarely need extra branch MCBs behind the strip.
  • Specified for UK, Ireland, Gulf and Hong Kong, China IT rooms that run on BS 1363 rather than IEC C13.
  • Mixed British and IEC C13 layouts are built to drawing: layout within 30 minutes, quotation within 1 hour.

Frequently Asked Questions

Do the outlets have individual fuses?

Yes. Every BS 1363 outlet carries a 13 A fuse behind the shutter, so a faulty appliance blows its own fuse and leaves the rest of the strip running.

Can 19 outlets on a 63 A feed be fully loaded?

Not at 13 A each. Continuous load should stay within the 63 A input, roughly ⁦9–10⁩ outlets at full 13 A; the rest is headroom for typical ⁦1–2⁩ A servers.

Is a 230 V version suitable for Ireland?

Yes — Ireland uses the same BS 1363 socket and 230 V supply, so the strip is a direct fit.

How is the strip fixed in a 600 mm deep cabinet?

Two M6 screws into the rear rail at 1358 mm centres, plus a bracket at the base. The 85 mm depth leaves the door swing and hot-aisle airflow clear.

Can it be shipped with a British 63 A plug instead of a terminal box?

Yes. We fit an IEC 60309 or BS 4343 plug on request, or leave a 2 m unterminated cable for site connection.

What is the lead time for a mixed British and C13 layout?

Layout drawing within 30 minutes, quotation within 1 hour, production ⁦7–15⁩ working days after the drawing is approved.