| Rack standard | 19-inch EIA-310 |
| Installation | Vertical (0U) |
| Mounting length | 1358 mm |
| Body dimensions (W×H) | 60 × 85 mm |
| Outlet configuration | 20× IEC C13 / C19 |
| Outlet rating | C13: 10 A; C19: 16 A |
| Input connection | OT terminal junction box |
| Input voltage | 110–250 V AC, 50/60 Hz |
| Max input current | 63 A |
| Rated power | Up to 15 kW at 250 V |
| Phase | Single-phase |
| Main breaker | Hydraulic magnetic breaker |
| Surge protection | None |
| Metering | LCD, total current / voltage / power / energy |
| Monitoring interface | TCP/IP + RS485 Modbus-RTU |
| Outlet switching | None |
| Housing | Cold-rolled steel, black powder coat |
| Operating temperature | -10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC / RoHS; built under ISO 9001 |
| Customisation | Socket mix, cable length and plug type to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
Temperature and humidity at the probe, with 1% humidity resolution, reported through the same network card as the electrical data. It lets you set a temperature threshold for the top of the rack, which is where recirculation shows up first.
No. The 63 A is the strip inlet; outlets stay at their own rating, 10 A for C13 and 16 A for C19. The inlet rating sets how much total load one strip can carry — enough for a fully populated 42U cabinet on a single feed.
42U to 47U cabinets, where the rail centres fall near this length. Measure the rail centres before ordering: a strip that is too short cannot be bolted at both ends, and one that is too long will not clear the cabinet door.
A thermal-magnetic MCB derates as the cabinet warms, so a circuit running near its rating trips on temperature rather than current. A hydraulic magnetic breaker responds to current only, which keeps the trip point stable from -10 °C to 45 °C.
Over SNMP v1/v2/v3 or Modbus TCP. Point the collector at the strip's IP address, enable the protocol in the web page, and current, power, energy, temperature and humidity appear as standard objects.
Yes. The C13 to C19 split, cord length and plug type are built to drawing. Send the layout and we return a drawing within 30 minutes and a quotation within the hour.