| Rack standard | 19-inch EIA-310 |
| Installation | Vertical (0U) |
| Height | 1U body section (44 mm) |
| Outlet configuration | 20× IEC C13 / C19 lockable |
| Outlet rating | C13: 10 A; C19: 16 A |
| Input connection | Hard-wired terminal block |
| Input voltage | 220–250 V AC, 50/60 Hz |
| Max input current | 16 A (32 A version to order) |
| Rated power | 3.5 kW at 16 A; 7.0 kW at 32 A |
| Phase | Single-phase |
| Main breaker | Hydraulic magnetic breaker |
| Surge protection | None |
| Metering | LCD, total current / voltage / power / energy |
| Monitoring interface | RS485 Modbus-RTU |
| Outlet switching | None |
| Housing | Aluminium alloy, black anodised |
| Operating temperature | 10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC / RoHS; built under ISO 9001 |
| Customisation | Socket mix, cable length and plug type to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
Both carry 20 lockable C13/C19 outlets. The 1U body is about 44 mm across instead of 66 mm, which matters when the gap behind the rear rail is tight or a cable tray runs close to the frame. If depth is not a constraint, the 1.5U version has more room for the meter and easier wiring.
They show that the outlet is carrying load, not how much. Per-outlet current would require a metered-outlet PDU. For branch-level figures use the LCD, which reports total current, voltage, power and energy for the whole strip.
Not on this model. The 1U body has no room for a replaceable SPD cartridge; choose the 1.5U 20-outlet metered PDU with 3-lamp SPD if the site needs surge diversion and a status lamp.
The input lands on a hard-wired terminal block with L, N and PE, and the housing is bonded to the same earth point. Cable entry is top or bottom, so feed direction follows the rack layout rather than forcing a loop.
Yes. Each strip takes its own address on the bus and the gateway polls them in sequence, so a row of 10 to 20 racks reports through one IP connection. Keep the bus below the recommended node count or split it with a repeater.
Seven to fifteen working days after the drawing is approved. Send the socket split, cord length and plug type, and we return a drawing within 30 minutes and a quotation within the hour.