| Rack standard | 19-inch EIA-310 |
| Installation | Vertical (0U) |
| Height | 1.5U body section (66 mm) |
| Outlet configuration | 20× IEC C13 / C19 lockable |
| Outlet rating | C13: 10 A; C19: 16 A |
| Input connection | Hard-wired terminal block |
| Input voltage | 220–250 V AC, 50/60 Hz |
| Max input current | 16 A (32 A version to order) |
| Rated power | 3.5 kW at 16 A; 7.0 kW at 32 A |
| Phase | Single-phase |
| Main breaker | Hydraulic magnetic breaker |
| Surge protection | 3-lamp SPD |
| Metering | LCD, total current / voltage / power / energy |
| Monitoring interface | RS485 Modbus-RTU |
| Outlet switching | None |
| Housing | Aluminium alloy, black anodised |
| Operating temperature | 10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC / RoHS; built under ISO 9001 |
| Customisation | Socket mix, cable length and plug type to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
A metered strip measures current, voltage, power and energy at the inlet but keeps every outlet permanently live. A switched PDU adds a relay per outlet so individual servers can be power-cycled remotely. This 20-outlet model is metered only, so the outlets stay on and the LCD reports consumption.
No. The meter sits in its own bay and unplugs from the strip, so a replacement goes in while the rack stays powered. That is why it is specified as hot-swap: you keep the branch circuit energised and lose metering for seconds, not hours.
0U is the mounting: the strip bolts vertically to the rack frame and uses no rack units of front space. 1.5U is the body section, roughly 66 mm across, which is the depth you need to allow behind the mounting rail.
A single master polls several slave strips on the same bus, each with its own address, so a full row of racks reports through one IP or serial gateway. Set addresses and baud rate on the front panel before commissioning.
Both. The 16 A feed gives 3.5 kW and the 32 A feed 7.0 kW at 220–250 V. Per-outlet current stays at 10 A for C13 and 16 A for C19, so the inlet rating never changes what a single server can draw.
Yes. Socket count, C13 to C19 ratio, cord length and plug type are built to drawing, and rated current follows the plug you choose. Send the rack layout and we return a drawing within 30 minutes and a quotation within the hour.