| Rack standard | 19-inch EIA-310 |
| Installation | Horizontal |
| Height | 1U body section (44 mm) |
| Outlet configuration | 36× IEC C13 + 4× IEC C19 |
| Outlet rating | C13: 10 A; C19: 16 A |
| Input connection | Hard-wired terminal block |
| Input voltage | 110–250 V AC, 50/60 Hz |
| Max input current | 32 A |
| Rated power | 8 kW at 250 V |
| Phase | Single-phase |
| Main breaker | Hydraulic magnetic breaker |
| Surge protection | None |
| Metering | LCD, total current / voltage / power / energy |
| Monitoring interface | RS485 Modbus-RTU |
| Outlet switching | None |
| Housing | Aluminium alloy, black anodised |
| Operating temperature | 10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC / RoHS; built under ISO 9001 |
| Customisation | Outlet count, cord length and plug type to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
A 42U cabinet of 1U servers needs 21 outlets for a redundant pair per shelf; 36 gives room for a fully populated cabinet plus switches and a spare pair. Fewer strips means fewer feeds, fewer breakers and less cable in the rack.
This bar is horizontal, so it consumes 1U of rack space but leaves both vertical rails free for cable management and does not foul the rear door. A vertical strip saves the rack unit but occupies rail length.
Yes, the count and the C13/C19 split are built to drawing. Note that the inlet stays at 32 A, so more C19 outlets change what you can plug in, not the total capacity.
At 250 V and 32 A the arithmetic gives 8 kW. On a 230 V supply the same 32 A gives about 7.4 kW, and on 208 V about 6.7 kW. Size the load against your actual site voltage, not the headline figure.
The top of the rack is the hottest zone because return air collects there. Fit the bar at the bottom if the cabinet runs above 35 °C at the top, and keep the inlet away from the hot aisle exhaust.
Seven to fifteen working days after drawing approval. Send the split and the inlet type, and we return a drawing within 30 minutes and a quotation within the hour.