| Rack standard | 19-inch EIA-310 |
| Installation | Horizontal |
| Height | 1U body section (44 mm) |
| Outlet configuration | 36× IEC C13 + 6× IEC C19 |
| Outlet rating | C13: 10 A; C19: 16 A |
| Input connection | Hard-wired terminal block, 5-wire |
| Input voltage | 380–415 V AC three-phase, 50/60 Hz |
| Max input current | 32 A per phase |
| Rated power | Up to 23 kW at 415 V |
| Phase | Three-phase |
| Main breaker | 3-pole breaker |
| Surge protection | None |
| Metering | LCD, current / voltage / power / energy per phase |
| Monitoring interface | RS485 Modbus-RTU |
| Outlet switching | None |
| Housing | Aluminium alloy, black anodised |
| Operating temperature | 10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC / RoHS; built under ISO 9001 |
| Customisation | Outlet count, cord length and plug type to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
Yes, 36 C13 plus 6 C19 instead of 4. The difference is the inlet: three-phase 32 A raises capacity from 8 kW to 23 kW, which is the point of this model.
Spread the C13 banks so each phase carries about a third. Put switches and storage on different phases from the server banks, then check the per-phase current on the panel after the cabinet is populated.
A dense cabinet usually has a switch pair, a storage pair and a UPS outlet or PDU feed to accommodate. Six C19 positions avoid adapters on those cords.
Not on this build. If the site needs SPD, ask for a version with a 3-lamp module; the horizontal body can take it on the models with a deeper section.
A 32 A three-phase circuit with neutral and earth, protected by a breaker rated for the cable. The strip's own 3-pole breaker protects the strip and outlets, not the feed cable.
Yes. Inlet rating, outlet count and split are built to drawing. Send the site voltage and the load schedule, and we return a drawing within 30 minutes and a quotation within the hour.