| Aisle dimensions (single row) | L × (2200–2400) × (2000–2200) mm, L < 15 m incl. air conditioners (excl. skylight flip height) |
| Aisle dimensions (double row) | L × (3200–3600) × (2000–2200) mm, L < 15 m incl. air conditioners (excl. skylight flip height) |
| Enclosed aisle width | 1200 mm or 1800 mm |
| Cabinet dimensions (W×D×H) | (600 / 800) × (1000 / 1100 / 1200) × (2000 / 2200) mm |
| Usable space | 42U / 47U |
| Cabinets per module | Single row: 3–24; double row: 6–40 |
| Installation | On raised floor, or directly on concrete ground |
| Reliability level | Tier II, or Tier III and above |
| Power system | 380/400/415 Vac, 50/60 Hz, 3Ph+N+PE |
| Protection rating | IP20 |
| UPS input voltage | 380/400/415 Vac, 50/60 Hz, 3Ph+N+PE |
| UPS rated capacity | 20–250 kVA |
| UPS configuration | N, N+1 or 2N |
| UPS input power factor | Integrated modular UPS ≥ 0.9; rack-mounted modular UPS 1.0 |
| UPS efficiency | ≥ 95% |
| Maintenance | Online hot-swappable |
| Battery arrangement | Internal or external |
| PDU mounting | Vertical mounting at cabinet front or rear |
| IT cabinet power feed | Utility / generator + utility / generator; UPS + UPS; UPS + utility / generator |
| Power distribution extras | Class C surge protection, 10-inch display, branch-circuit monitoring |
| Power system certification | CCC |
| Cooling options | In-row DX / chilled water; room-level DX / chilled water |
| Cooling mode | Direct expansion (air-cooled) or chilled water |
| AC power supply | Indoor and outdoor units powered separately |
| AC installation | Indoor unit on raised floor; outdoor unit on level concrete ground |
| Compressor type | In-row: variable-frequency; room-level: fixed-frequency |
| Fan type | EC fans |
| Air supply mode | In-row: horizontal airflow; room-level: underfloor air supply |
| Indoor unit dimensions (W×D×H) | In-row: 300 × 1200 × 2000 mm or 600 × 1200 × 2000 mm; room-level per selection table |
| Cooling certification | CQC energy-saving certification |
| Monitoring modules | Centralized management, access control, video surveillance, asset management, battery monitoring |
| Monitoring access | Remote web access, local 10-inch touchscreen, mobile app (optional) |
| Alarm methods | WeChat, local sound-and-light, SMS, email and phone alarms |
| Monitoring certification | Software copyright, software test report |
| Rack certification | Seismic test report, load-bearing test report |
| Standards compliance | ANSI/EIA-310-D, IEC 60297-2, DIN 41491 Part 1, DIN 41494 Part 7, GB/T 3047.2-92 |
| Energy saving | Up to 30% through hot/cold air isolation |
| Applications | New-build, retrofit and expansion data centers in finance, government, telecom, energy, transportation, healthcare, education and manufacturing |
| Door access | Remote control, card, password or sensor |
| Response | Engineering drawings in 30 minutes, quotation in 1 hour |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
It encloses the cold aisle between cabinet rows so cold and hot air are fully isolated, with no turbulence or airflow short-circuiting. Cooling efficiency rises well above single-cabinet levels, equipment density increases, less floor space is needed, and energy consumption drops by up to 30%.
The enclosed aisle is 1200 mm or 1800 mm wide. A single-row module holds 3–24 cabinets and a double-row module 6–40, with a total length under 15 m including air conditioners. Cabinets are 600 or 800 mm wide, 1000–1200 mm deep and 2000 or 2200 mm high, providing 42U or 47U of usable space.
In-row or room-level air conditioners, either direct-expansion (air-cooled) or chilled water. In-row units use variable-frequency compressors and EC fans with horizontal airflow, sized 300 × 1200 × 2000 mm or 600 × 1200 × 2000 mm; room-level units use fixed-frequency compressors with underfloor air supply.
The system runs on 380/400/415 Vac, 50/60 Hz, 3Ph+N+PE. A modular UPS of 20–250 kVA can be configured N, N+1 or 2N with at least 95% efficiency and online hot-swap maintenance, and batteries are installed internally or externally. Rack PDUs mount vertically at the cabinet front or rear, and the distribution cabinet adds Class C surge protection, a 10-inch display and branch-circuit monitoring.
A fire-rated skylight in the aisle roof opens under gravity, allowing the gas fire-suppression system to discharge directly into the cold aisle area — safe and reliable. Fire linkage includes sound-and-light alarms, smoke sensors and temperature-humidity sensors.
The enclosed track-mounted double doors open by remote control, card, password or sensor. The monitoring system covers centralized management, access control, video surveillance, asset management and battery monitoring, accessible via remote web, a local 10-inch touchscreen or an optional mobile app, with alarms pushed by WeChat, SMS, email and phone.