| Rack standard | 19-inch EIA-310 |
| Installation | Vertical (0U) |
| Mounting length | 881 mm |
| Body dimensions (W×H) | 62 × 63 mm |
| Outlet configuration | 10× IEC C13 / C19 |
| Outlet rating | C13: 10 A; C19: 16 A |
| Overload protection | Yes, separate overload protection switch |
| Input connection | OT terminal junction box |
| Input voltage | 380 V AC three-phase (220–250 V phase to neutral), 50/60 Hz |
| Max input current | 63 A per phase |
| Phase | Three-phase |
| Main breaker | Hydraulic-magnetic breaker, 3-pole 63 A |
| Surge protection | None |
| Cable entry | Top or bottom |
| Housing | Cold-rolled steel, black powder coat |
| Operating temperature | 10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC; built under ISO 9001 |
| Customisation | Outlet mix, socket pattern and cable length to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
Because heat changes the answer. A thermal-magnetic miniature breaker trips earlier in a 45 °C aisle than its label suggests, and nuisance trips in a mining room cost hashrate. A hydraulic-magnetic breaker is temperature-stable, so the trip point stays where it was set.
A local, visible reset. After a trip, the operator resets at the strip instead of walking back to the distribution panel, and the switch position tells you the strip tripped rather than lost its feed.
Spread machines so each phase carries a similar current. With ten positions the split is roughly four, three and three; keep the biggest supplies off a single phase and check the current on each phase after the first week.
It suits half-height racks, wall cabinets and short control frames rather than a full 42U row. Measure the rear rail spacing before ordering; if the run is full height, the 1269 mm and 1075 mm versions cover that.
Yes. The C13 to C19 ratio is built to drawing, and the breaker and terminal block are sized to the feed you specify.
No. It is a breaker-protected strip: hydraulic-magnetic breaker, overload switch, ten outlets. Metered versions of the same body length are available if you need per-port current.