| Rack standard | 19-inch EIA-310 |
| Installation | Horizontal |
| Mounting length | 1900 mm |
| Body dimensions (W×H) | 100 × 60 mm |
| Outlet configuration | 12× NEMA L22-30R |
| Outlet rating | 30 A per outlet, three-phase |
| Input connection | OT terminal junction box |
| Input voltage | 365–480 V AC three-phase, 50/60 Hz |
| Max input current | 200 A per phase |
| Phase | Three-phase |
| Main breaker | Hydraulic-magnetic breaker, 3-pole |
| Surge protection | 1-lamp SPD |
| Cable entry | Top or bottom |
| Housing | Cold-rolled steel, black powder coat |
| Operating temperature | 10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC; built under ISO 9001 |
| Customisation | Outlet count, phase grouping and cable length to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
Because of the load and the environment. L22-30R is a 30 A three-phase twist-lock connector: it carries a real machine feed and it locks, so vibration cannot walk it out. C13 would be under-rated and unlatched within a month.
The feed, not the outlets, sets the ceiling. Twelve L22-30R at 30 A each is more outlet capacity than a 200 A three-phase supply can deliver at once, which is normal: diversity is what makes a row of miners work. Size the feed from measured machine draw, not from the sum of outlet ratings.
Three groups of four, one group per phase, each group marked on the panel. Keep the machine load per phase similar; a phase carrying twice the others will trip the main breaker long before the strip is fully used.
It fits 19-inch racks with a wide rear channel and is intended for rows where the strip runs across rather than down. Check the rear rail width and the cable bend radius before ordering; a vertical version of the same outlet count is available.
No. The strip is rated 365–480 V three-phase and the outlets are the 480 V class L22-30R. What matters on site is that the upstream protection matches the 480 V fault level, which is why the hydraulic-magnetic breaker is specified rather than a miniature breaker.
Yes. Outlet count, phase grouping, cable length and terminal type are built to drawing. Drawings within 30 minutes, quotation within one hour.