| Rack standard | 19-inch EIA-310 |
| Installation | Vertical (0U) |
| Mounting length | 1269 mm |
| Body dimensions (W×H) | 65 × 83 mm |
| Outlet configuration | 24× GB three-pin |
| Outlet rating | 10 A per outlet |
| Input connection | OT terminal junction box |
| Input voltage | 380 V AC three-phase (220–250 V phase to neutral), 50/60 Hz |
| Max input current | 63 A per phase |
| Phase | Three-phase |
| Main breaker | 3-pole breaker, 63 A |
| Surge protection | None |
| Cable entry | Top or bottom |
| Housing | Cold-rolled steel, black powder coat |
| Operating temperature | 10–45 °C |
| Relative humidity | 0–90% RH, non-condensing |
| Included accessories | M6×16 screws, user manual |
| Certification | CE / EMC; built under ISO 9001 |
| Customisation | Outlet count, socket pattern and cable length to drawing |
| Lead time | 7–15 working days after drawing approval |
Datasheet, manual and drawings for this product (PDF).
Our engineers reply within 24 hours on business days.
Tel: +86-574-63783045
Email: ricky@idcpdu.com
Tell us your requirements — our sales team will get back to you with a quotation.
Because the machines come with GB plugs. Putting an IEC strip in a Chinese mining rack means twenty-four adapters, twenty-four extra contact points and twenty-four things to fall out. A GB strip removes all of them.
The outlets are spread across L1, L2 and L3, roughly eight per phase, and the 3-pole breaker isolates all three together. Balance the machines across phases when you plug them in; a single-phase-heavy pattern on one phase trips the breaker while two phases are still lightly loaded.
GB 2099.1 three-pin outlets are rated 10 A, which suits a miner drawing around 2 kW at 220 V. If you need 16 A outlets, the strip is built to drawing with the 16 A pattern and a matching breaker.
Yes. The 65 × 83 mm section sits inside the rear channel between the rails, and the 1269 mm mounting length matches the rear rail spacing of a 42U cabinet, so it does not eat cable space or block a blanking panel.
Not on this model. It is a breaker-protected distribution strip: one 3-pole breaker, twenty-four outlets, no electronics to fail in a hot hall. Metered and switched versions of the same body length are available if you need per-port data.
Yes. Outlet count, GB pattern, cable length and terminal type are built to drawing. Drawings within 30 minutes, quotation within one hour.